High-quality residual current circuit-breaker/miniature circuit-breaker with overcurrent protection independent of mains voltage; contact position display red-green; terminal rear plug protection; tri-stable slide catch—enables removal from an existing closure assembly; comprehensive accessory product range can be retrofitted; wide range of rated fault currents; rated operational currents up to 40 A; trip types B,C; rated switching capacity 10 kA; suitable for use in the free (on-site power and outdoor distribution board) to -25 °C
- Mærkestrøm: 10 A
- Nominel fejlstrøm: 0,03 A
- Antal poler (total): 2
- Fejlstrømstype: A
- Udløserkarakteristik: C
- Afbrydelsesegenskab: Korttidsforsinket
- Antal beskyttede poler: 1
- Betinget nominel kortslutningsstrøm: 10 kA
- Egnet til skjult installation: Nej
- Energibegræsningsklasse: 3
- Fejludløserbeskyttelse: Nej
- Forureningsgrad: 2
- Frekvens: 50 Hz
- Indbygningsdybde: 69,5 mm
- Indmuringsmontage: Nej
- Kapslingsklasse (IP): IP20
- Max ledertværsnit entrådet: 1 - 25 mm²
- Max ledertværsnit flertrådet: 1 - 25 mm²
- Med aflåsningsmekanisme: Nej
- Modul-bredde: 2
- Mærkespænding: 230 V
- Nominel isolationsspænding Ui: 440 V
- Nominel kortslutningsbrydeevne Icn iht. EN 61009-1: 10 kA
- Nominel kortslutningsstrøm i forhold til EN 61009: 10 kA
- Nominel kortslutte bryde kapacitet IEC 60947-2: 0 kA
- Nominel mærkespænding (Uimp): 4 kV
- Omgivelsestemperatur under drift: -25 - 40 °C
- Overspændingskategori: 3
- Parallell omkobling N-neutral: Ja
- Spændingstype: AC
- Fødevarekontaktmateriale: Nej
- REACH: Nej